185
Reference Manual
00809-0100-4811, Rev DA
Appendix C: Rosemount 3300 Series with HART
®
to Modbus
®
Converter
January 2015
Rosemount 3300 Series with HART
®
to Modbus
®
Converter
The transmitter will continue to use a communication protocol once communication has been
established.
To configure the 3300 level transmitter using RCT and the MA (+), MB (-) terminals, do the
following:
1. Connect the RS-485 Converter to the MA (+), MB (-) terminals.
2. Connect the power wires (or cycle power) to the transmitter.
3. Wait 20 seconds.
4. In RCT, select Poll Address in the drop-down list (also see note below). Select the
button to the left of the drop-down list to start polling.
5. After connection to the transmitter, perform the necessary configuration.
6. When the configuration is completed, disconnect the RS-485 Converter, connect the
Modbus communication wires, and cycle power to the transmitter
7. Verify communication between the transmitter and the RTU is established (can take up
to 60 seconds from startup).
Note
If there are multiple 3300 Modbus units on the bus with HART address 1, it will not be possible
to establish communication (by default the transmitters have HART address 1). To establish
communication in this case, make sure the 3300 transmitter is alone on the bus. Disconnect or
turn off power from any other devices.
C.6.2 Connect to the HART terminals
To configure the Rosemount 3300 Series Transmitter, connect the communicator or PC to the
HART terminals using a HART modem, see Figure C-3 on page 182. Both the configuration tool
and the RS-485 bus can be connected simultaneously. Configuration data is sent with HART
commands through the HMC to the 3300 transmitter electronics, as illustrated in Figure C-1 on