Reference Manual
00809-0100-4811, Rev DA
Section 6: Service and Troubleshooting
January 2015
Service and Troubleshooting
6.3.3 Disturbances at the top of the tank
Using the Trim Near Zone function
For transmitters using the Guided Wave Radar technology, the performance in the Near Zone
(referred to as the region between 0-1.6 ft (0-0.5 m) below the upper reference point) is
normally somewhat limited. However, the Rosemount 3300 Series Transmitter is equipped with
a software functionality that minimizes the upper transition zone. The factory setting is
normally sufficient and does not need to be repeated after installation.
However, since the setting is optimized depending on actual installation, further trimming may
be necessary in the case of unfavorable conditions. For example, this may be the case if a single
lead probe is mounted in a small nozzle, or if there are disturbing obstacles in the near zone. The
trimming means that the measurement performance in the near zone is maintained even under
these conditions and prevents false echo indication.
To trim the near zone perfomance, do the following:
1. Make sure the product level is below the near zone region
(0-1.6 ft (0-0.5 m) below the upper reference point).
2. Start RCT.
3. Select the Device Commands option from the View menu.
4. Open the Details folder.
5. Select the Trim Near Zone option.
6. Select the Update option and click OK.
Note
The Trim Near Zone function should only be used for reducing impact from constant
disturbances. It is not suitable for occasional disturbances.
To reset the transmitter to factory settings do the following:
1. Start RCT.
2. Select the Device Commands option from the View menu.
3. Open the Details folder.
4. Select the Trim Near Zone option.
5. Select the Reset to Factory Settings option and click OK.
Changing the Upper Null Zone
Measurements are not performed within the Upper Null Zone (UNZ). By setting the UNZ
parameter to zero, measurements can be performed in the region close to the flange (near
zone). However, it is very important that there are no disturbances in that region if UNZ is set to
zero.