100
Reference Manual
00809-0100-4811, Rev DA
Section 6: Service and Troubleshooting
January 2015
Service and Troubleshooting
6.3 Service
6.3.1 Analog output calibration
To calibrate the analog output current, do the following:
1. Start RCT and make sure the transmitter communicates with the PC (see section Basic
Configuration/Start-Up ).
2. Under Tools, select the Device Cmds icon,
or
select the Device Commands option from the View menu.
3. Open the folder named Diag and double-click the Fixed Current Mode option.
4. Set the output current to 4 mA.
5. Measure the output current.
6. Open the folder named Details.
7. Select the Trim DAC Zero option and enter the measured output current.
8. In the Diag folder, double-click the Fixed Current Mode option, and set the output
current to 20 mA.
9. Measure the output current.
10. In the Details folder double-click the Trim DAC Gain option, and enter the measured
output current.
11. In the Diag folder double-click the Fixed Current Mode option, and set the output
current to 0 mA in order to leave the Fixed Current Mode.