Reference Manual
00809-0100-4811, Rev DA
Appendix A: Reference Data
January 2015
Reference Data
Table A-5. Measuring Range and Minimum Dielectric Constant When Using Remote Housing
Different parameters (factors) affect the echo and therefore the maximum measuring range
differs depending on application according to:
Disturbing objects close to the probe
Media with higher dielectric constants (
r
) give better reflection and allow a longer
measuring range
Surface foam and particles in the tank atmosphere may affect measuring performance
Heavy coating or contamination on the probe should be avoided since it can reduce
measuring range and might cause erroneous level readings
Note
See Table A-5 on page 129 for the measuring range when using the remote housing.
Interface measuring range
Target applications include interfaces between oil; oil-like and water; and water-like liquids with
a low (< 3) upper product dielectric constant and a high (>20) lower product dielectric constant.
For such applications, the maximum measuring range is only limited by the length of the
coaxial, rigid twin, and rigid single lead probes.
For the flexible twin lead probe, the maximum measuring range will be reduced depending on
the maximum upper product thickness according to the diagram (inset, right).
Example: If the upper product dielectric constant is 2, and the upper product thickness is 5 ft.
(1.5 m), the maximum measuring range is 75.5 ft. (23 m).
However, characteristics vary between different applications.
Rigid single lead /
segmented rigid
single lead
Flexible
single lead
Coaxial
Rigid
twin lead
Flexible
twin lead
Maximum
measuring range
9 ft. 10 in. (3 m) -
for 8 mm probes
(code 4A)
14 ft. 9 in. (4.5 m) -
for 13 mm probes
(code 4B, 4S)
72 ft. (22 m)
19 ft. 8 in.
(6 m)
9 ft. 10 in.
(3 m)
72 ft. (22 m)
Minimum dielectric
constant with
1 m remote housing
2.7 (2.0 if installed
in a metallic bypass
or stilling well)
(1)
(1) May be lower depending on installation.
2.7 up to 36 ft. (11 m)
6 up to 66 ft. (20 m)
10 up to 72 ft. (22 m)
1.5 2.1
1.7 up to 33 ft. (10 m)
2.2 up to 66 ft. (20 m)
2.6 up to 72 ft. (22 m)
Minimum dielectric
constant with
2 m remote housing
3.3 (2.2 if installed
in a metallic bypass
or stilling well)
(1)
3.2 up to 36 ft. (11 m)
8 up to 67 ft. (20.5 m)
1.6 2.5
1.8 up to 33 ft. (10 m)
2.4 up to 67 ft. (20.5 m)
Minimum dielectric
constant with
3 m remote housing
3.8 (2.5 if installed
in a metallic bypass
or stilling well)
(1)
3.7 up to 36 ft. (11 m)
11 up to 62 ft. (19 m)
1.7 2.8
2.0 up to 33 ft. (10 m)
2.7 up to 62 ft. (19 m)