Appendix C: Rosemount 3300 Series with HART
®
to Modbus
®
Converter
January 2015
Rosemount 3300 Series with HART
®
to Modbus
®
Converter
Figure C-2. Field Wiring Connections
C.5.1 Connection terminals
The connection terminals are described in Tab le C -1 below:
Table C-1. Connection Terminals
Connector label Description Comment
HART + Positive HART connector Connect to PC with RCT software,
Field Communicator, or other HART
configurators.
HART - Negative HART connector
MA (+) Modbus RS-485 B connection (RX/TX+)
(1)
(1) The designation of the connectors do not follow the EIA-485 standard, which states that RX/TX- should be referred to as 'A' and
RX/TX+ as 'B'.
Connect to RTU
MB (-) Modbus RS-485 A connection (RX/TX-)
(1)
PWR + Positive Power input terminal
Apply +8 Vdc to +30 Vdc (max. rating)
PWR - Negative Power input terminal
RS-485 Bus
B
A
Power
Supply
HART
+
120
120
In case it is the last
transmitter on the
bus, connect the
120
termination
resistor
120
HART
-