Appendix B: Product Certifications
January 2015
Product Certifications
Special Conditions For Safe Use (X):
1. The apparatus is not capable of withstanding the 500V test as defined in Clause 6.3.13
of EN60079-11:2012. This must be considered in any installation.
2. The Rosemount 3300 Series enclosure is made of aluminum alloy and given a
protective polyurethane paint finish; however, care should be taken to protect it from
impact or abrasion if located in zone 0.
3. The probes may contain plastic materials greater than 4 cm
2
or be coated with plastic
and these can present an electrostatic risk if rubbed or placed in a fast moving air flow.
4. The probes may contain light alloys which can present a risk from frictional ignitions.
Care should be taken to protect them from mechanical impact during use or
installation.
I1 Intrinsic safety:
Certificate: BAS02ATEX1163X
0575
II 1 G Ex ia IIC T4 Ga (-50 °C
T
a
+70 °C)
U
i
= 30 V, I
i
= 130 mA, P
i
= 1.0 W, L
i
= C
i
= 0
Ambient temperature limit: -50 °C
T
a
+70 °C
Functional voltage range: 11-42 Vdc
Intrinsically safe version: 11-30 Vdc
Approval valid for HART option.
Figure B-4. Approval Label ATEX (BASEEFA) and Name Plate